NOVUS AUTOMATION 1/2
TxIsoLoop-1 / TxIsoLoop-2
LOOP-POWERED ISOLATORS - OPERATING MANUAL V1.0x D
INTRODUCTION
The TxIsoLoop-1 and TxIsoLoop-2 are 0(4)-20 mA signal isolators
with one and two channels respectively. They provide signal
protection by electrically isolating the input signal from the output.
The 4-20 mA input is measured and an identical isolated signal is
produced at the output. Its power is obtained from the 0(4)-20 mA
input loop, dropping the need for an external power supply.
CHARACTERISTICS
Input/output galvanic isolation.
Models for 1 or 2 channels.
Don’t require power supply.
High accuracy.
Calibration free.
ESPECIFICAÇÕES
Input Signal (INPUT): 0 to 20 mA; 4 to 20 mA
(check minimum current for proper operation)
Max. Input voltage (Vin max.): 32 Vdc
Voltage drop input/output without protection (Vdrop): < 3 Vdc
Voltage drop input/output with protection (Vdrop): < 5 Vdc
Output Signal (OUTPUT): 0(4) to 20 mA
Max. Load (RL): 1450 R
Accuracy: 0.2 % FS @ 0 a 60 ºC / RL= 250 R
0.3 % FS @ -20 a 75 ºC / RL= 250 R
Operating current: > 0,1 mA
Overload: < 40 mA; < 32 Vdc
Response time: 2 ms @ RL= 250 R
Isolation: 3000 Vac / 10 s
240 Vac continuous
EMC: EN 61326-1
Ambient temperature range: -20 to + 75 ºC
Humidity: 20 a 90 %
Case: ABS (60 %) + PC (40 %). Protection: IP40
Wire gauge for connections: 0.14 a 1.5 mm²
Recommended torque: 0.8 Nm
Terminal blocks injected in Polyamide.
ELECTRICAL INSTALLATION
For proper operation, the TxIsoLoop requires some minimum
voltage in the input loop. This voltage can be found in two ways:
1. In type source devices (transmitters, controllers, etc), this voltage
is provided by the device itself.
Fig. 1TxIsoLoop typical connections
The minimum operating voltage can be calculated by the equation
below:
V
1
= V
in
Where:
V
in
= V
drop
+ ( I
out(máx)
x R
L
)
I
in
= I
out
2. In sink type devices (2-wire transmitters) the energy is provided by
an external power supply in series in the loop, as shown in Fig. 2.
Fig. 2TxIsoLoop used to isolate a 2-wire transmitter
In this arrangement, the power supply must provide enough voltage
such as power both the 2-wire transmitter and the TxIsoLoop.
The minimum voltage required to allow proper operation can be
obtained from the equation below:
V
1
= V
b
+
V
in
Where:
V
1
= Power supply voltage
V
b
= Voltage required by the 2-wire
transmitter
V
in
= V
drop
+ ( I
out(máx)
x R
L
)
I
in
= I
out
Vista de página 0
1 2

Resumo do Conteúdo

Página 1 - TxIsoLoop-1 / TxIsoLoop-2

NOVUS AUTOMATION 1/2 TxIsoLoop-1 / TxIsoLoop-2 LOOP-POWERED ISOLATORS - OPERATING MANUAL V1.0x D INTRODUCTION The TxIsoLoop-1 and TxIsoLoop-2 ar

Página 2 - SUPPORT AND MAINTENANCE

NOVUS AUTOMATION 2/2 ELECTRICAL WIRING The figure below shows the wiring scheme. Fig. 3 – TxIsoLoop-1 connections Fig. 4 – TxIsoLoop-2 connectio

Comentários a estes Manuais

Sem comentários